Air Cooled Industrial Recirculating Chiller Water Cooling System
Air Cooled Industrial Recirculating Chiller Water Cooling System
Introduction:
Working conditions of the unit for testing the nominal refrigerating capacity: Outlet temperature: 7°C;
Water flow rate: 0.172 m3/(h•kW);
Outdoor temperature: 35°C
Working conditions of the unit for testing the nominal heating capacity:
Outlet temperature: 45°C;
Water flow rate: 0.172 m3/(h•kW);
Outdoor psychrometric difference: 7°C or 6°C
Water resistance includes differential water pressure of the unit and that of the affiliated Y-shape filter.
For combined units, the manufacturer does not offer general water pipes and they must be prepared and installed on site.
Diameter of the pipes should comply with design standards.
A modular unit can be combined by same or different modules based on actual requirements; up to 16 modules can be built into a modular unit. The parameters listed in the table above are for commonly combined units.
Power distribution and wiring are subject to unit nameplates or installation guide.