Temperature Controller With RS485 Modbus-RTU Module Type Controllers
Digital temperature controller features
1. Can be connect the following sensors and signals to the universal input(K.E,J.T.S,R,B,N,PT100).
2. Can be easily set the optimum PID constants by performing AT (auto-tuning) with the limit cycle method,or ON-OFF Control Mode.
3. Can be output an alarm when the deviation, process value, set point, or manipulated value reaches a specified value.
4. With any model that supports communications, can be use communications , Modbus-RTU(standard)
5. With any model that provides a transfer process value as a 4 to 20 mA or 1 to 5 V transfer output.
Main parameter list
Name | Manual |
---|---|
Setting value | Set the temperature set value (SV) which is the target value for control |
Alarm 1 | Please refer to ALP for the alarm mode suitable. Alarming when the program sections is breaking up. |
PV Bias | The value set in the PV bias is added to the actual input value to correct the input value. |
Proportional band | Set when PI or PID control is performance. For heating / cooling PID action. When P=0,the meter is ON/OFF control |
Integral time | Eliminates offset occurring in proportional control. |
Derivative time | Prevents overshoot and/or undershoot caused by integral action effect.. |
PID control cycle. | Control response time |
Digital Filter | This is a 1st-order lay filter by software prepared in order to reduce fluctuations of measured value (PV) by noise. |
Differential gap | When the control is ON/OFF control(P=0) Relay contact may repeat its turning ON and OFF due to input fluctuation if measured value (PV) is near the alarm set value.the differential gap setting can prevent the relay contact from ON or OFF repetition. |
Decimal point position selection | Set the position of the decimal point for the measured value to be displayed. |
Output limiter high | Output limiter low to 200 |
Output limiter low | 0 to Output limiter high |
Autotuning (AT) with learning function | 1: Autotuning (AT) with learning start 0: Autotuning (AT) with learning stop Turns OFF automatically when the AT with learning function is completed. |
Set data lock | LOCK=0, Set value (SV) and parameter can be set. LOCK=1,Only set value (SV) can be set. LOCK>1, Set value (SV) and parameter cannot be set. |
Input type1 | Cu50(–50.0~150.0℃); Pt100 (–199.9~600.0℃; ) K( -30.0~1300℃); E( -30.0~700.0℃); J (-30.0~900.0℃); T( -199.9~400.0℃); S( -30~1600℃); |
Input type2 | 0~5V/0~10mA; 1~5V/4~20mA; |
Control output | 0:no output 1:Relay output 2:Voltage output (for driving SSR) 3:Zero-cross output(for driving Triac) 4:PID linear current output(4-20mA /0-10v) (A single functional) |
AUX output Opt. | 0:no output; 1:RS232 or RS485; 2:contact the micro-printer; 3:transmitter 0~10mA 4:transmitter4~20mA |
Alarm type | 0: Alarm function OFF; 1: Process high alarm; 2:Process low alarm; 3:Process high and low alarm.(H1 and L2) 4: Deviation High alarm ; 5:Deviation low alarm; 6:Deviation High and Low alarm..(H1 and L2) 7: Out of band alarm. 8:Band alarm. |
System function Opt. | 0::reverse control(heating) 1::positive control(cooling) |
Range high | The control is displayed after the Input type and Input range. |
Range low | |
Address | Communication address can be set from 0 to 255 |
Communication speed | 1200; 2400; 4800; 9600; |